• Schneider TM3DQ16R Module TM3 - 16 outputs relays

Schneider TM3DQ16R Module TM3 - 16 outputs relays

Main
range of product
Modicon TM3
product or component type
Discrete output module
range compatibility
Modicon M221
Modicon M241
Modicon M251
discrete output type
Relay normally open
discrete output number
16
discrete output logic
Positive or negative
discrete output voltage
240 V AC for relay output
30 V DC for relay output
discrete output current
2000 mA for relay output
Complementary
discrete I/O number
16
current consumption
0 mA at 24 V DC via bus connector at state off
75 mA at 24 V DC via bus connector at state on
response time
10 ms for turn-on
5 ms for turn-off
mechanical durability
20000000 cycles
minimum load
10 mA at 5 V DC for relay output
local signalling
1 LED per channel green for output status
electrical connection
Removable screw terminal block pitch 3.81 mm with 10 terminal(s) of 1.5 mm² connection capacity for outputs
cable distance between devices
Unshielded cable: <= 30 m for relay output
insulation
2300 V AC between output and internal logic
750 V AC between outputs
1500 V AC between output groups
marking
CE
mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Plate or panel with fixing kit
height
90 mm
depth
84.6 mm
width
27.4 mm
product weight
0.145 kg

Environment
standards
EN/IEC 61131-2
EN/IEC 61010-2-201
product certifications
cULus
C-Tick
resistance to electrostatic discharge
4 kV (on contact) conforming to EN/IEC 61000-4-2
8 kV (in air) conforming to EN/IEC 61000-4-2
resistance to electromagnetic fields
10 V/m at 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m at 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m at 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
resistance to magnetic fields
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
resistance to fast transients
2 kV for relay output conforming to EN/IEC 61000-4-4
surge withstand
1 kV for I/O (DC) in common mode conforming to EN/IEC 61000-4-5
resistance to conducted disturbances
10 Vrms at 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 Vrms at spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
electromagnetic emission
Radiated emissions, test level: 40 dBμV/m QP with class A, condition of test: 10 m (radio frequency: 30...230 MHz) conforming to EN/IEC 55011
Radiated emissions, test level: 47 dBμV/m QP with class A, condition of test: 10 m (radio frequency: 230...1000 MHz) conforming to EN/IEC 55011
ambient air temperature for operation
-10...55 °C for horizontal installation
-10...35 °C for vertical installation
ambient air temperature for storage
-25...70 °C
relative humidity
10...95 % without condensation in operation
10...95 % without condensation in storage
IP degree of protection
IP20 with protective cover in place
pollution degree
2
operating altitude
0...2000 m
storage altitude
0...3000 m
vibration resistance
3.5 mm (vibration frequency: 5...8.4 Hz) on DIN rail
3 gn (vibration frequency: 8.4...150 Hz) on DIN rail
3.5 mm (vibration frequency: 5...8.4 Hz) on panel
3 gn (vibration frequency: 8.4...150 Hz) on panel
shock resistance
15 gn (test wave duration:11 ms)